Sustainable District-Heating Transition in Poland: The Case of the City of Ustka
ポーランドにおける持続可能な地域暖房への移行:ウストカ市の事例 (AI 翻訳)
Ireneusz Zagrodzki, Mateusz Bryk, Piotr Józef Ziółkowski, Tomasz Kowalczyk, Pedro Jesus Cabrera Santana, Janusz Badur
🤖 gxceed AI 要約
日本語
ポーランドの地域暖房システムのエネルギー移行を、実運用データと市場シグナルを組み合わせたOPEXベースのスクリーニング枠組みで分析。ウストカ市を事例に、CHP、ヒートポンプ、蓄熱、ピークボイラーを含むハイブリッド構成を比較し、最適な容量配分を提示。地中熱交換器の実地制約を検証し、運用上有利な構成が実現不可能な場合があることを示した。
English
This study presents an OPEX-based screening framework for district heating transition, combining real operational data with market signals. A case study of Ustka, Poland, compares hybrid configurations including CHP, heat pumps, and storage, identifying optimal capacities. It verifies practical feasibility, showing that the lowest OPEX option may be constrained by local resources, offering a replicable approach for Polish operators.
Unofficial AI-generated summary based on the public title and abstract. Not an official translation.
📝 gxceed 編集解説 — Why this matters
日本のGX文脈において
日本の地域熱供給事業者にとっても、実データと市場価格を用いたハイブリッド構成のスクリーニング手法は参考になる。特に、地中熱などの再生可能エネルギー導入時の実地制約を考慮する点は、日本の都市部での導入検討に示唆を与える。
In the global GX context
This study contributes to global district heating transition literature by integrating real operational data with market signals and local constraints. It offers a replicable framework for screening hybrid systems, relevant for regions with similar heating infrastructure. The emphasis on practical feasibility over dispatch-model favorability is a valuable lesson for transition planning worldwide.
👥 読者別の含意
🔬研究者:Provides a replicable OPEX-based screening framework for hybrid district heating systems, integrating real data and local constraints.
🏢実務担当者:Offers a practical approach for district heating operators to evaluate hybrid transition pathways under real market conditions.
🏛政策担当者:Highlights the importance of considering local resource constraints in energy transition planning, informing policy for sustainable heating.
📄 Abstract(原文)
The energy transition of district heating systems in Poland requires the simultaneous consideration of energy efficiency, operating costs, technical feasibility, and local environmental constraints. This study addresses an identified gap in the literature by combining real operational time series from a municipal district heating system with time-resolved market signals and site-specific resource constraints in a single OPEX-based operational screening framework. A case study is conducted for the city of Ustka using a configuration-based comparison of hybrid supply systems that include a gas-fired combined heat and power (CHP) unit, air-source and ground-source heat pumps, thermal energy storage, and a peak-load boiler. The optimisation model was implemented in MS Excel using the GRG Nonlinear algorithm (Solver) and was driven by the district heating operational data for 2021–2022 together with electricity and natural gas prices from the Polish Power Exchange day-ahead market (TGE RDN), evaluated under both hourly and daily settlement assumptions. The results indicate an optimal capacity split of 1.2 MWel/1.3 MWth for the CHP unit and 1.5 MWel/3.0 MWth for the heat pump system, supported by a required peak boiler capacity of 8.23 MWth. Within the adopted OPEX-based assessment, the lowest value of the unit heat generation indicator was obtained for the CHP-led configuration with combined ground-source and air-source heat pumps (38.45–38.55 PLN/GJ). A distinctive element of the study is the explicit verification of whether an operationally favourable configuration remains practically feasible when local resource constraints are considered. The site assessment indicates limited practical feasibility of the borehole heat exchanger at the analysed location in Ustka, showing that the lowest OPEX result should not be interpreted as a final investment recommendation. The study provides a replicable approach for the Polish district heating operators to screen hybrid transition pathways under real market conditions and to avoid technology choices that are favourable in dispatch models but constrained in practice. From a sustainability perspective, the proposed framework supports more energy-efficient, resilient, and locally feasible district heating transition planning in municipal heat systems.
🔗 Provenance — このレコードを発見したソース
- openalex https://doi.org/10.3390/su18104971first seen 2026-06-07 04:39:04 · last seen 2026-06-14 04:36:12
🔔 こうした論文の新着を逃したくない方は キーワードアラート に登録(無料・3キーワードまで)。
gxceed は公開メタデータに基づく研究支援データセットです。要約・翻訳・解説は AI 支援で生成されています。 最終的な解釈・検証は利用者が原典資料に基づいて行うことを前提とします。